Chaque ligne est la conclusion — ou l'action qui l'a réglée — d'une intervention réelle. Quand la note vient d'un compte rendu chinois, l'original est conservé dessous.

Les notes de terrain sont citées dans la langue dans laquelle elles ont été rédigées.

24 notes de terrain sur ce thème

  • The pierce heights at every stage are correct, which points at the datum capacitance the height controller captured — that is what makes the following height wrong.
  • The F following indicator only appears after following for a while. That points to an unstable height controller producing the following pauses.
  • Switching following on and off repeatedly, the Z coordinate keeps decreasing — the datum is drifting.
  • A DIF value below 30 means the jitter is not interference on the capacitive sensor. Re-calibrate the height controller: make sure there is a sheet under the head, press Follow on the controller and watch whether the head jitters.
  • On the height controller press F1 to enter calibration, then press 2 and follow the prompts to redo the floating-head calibration. This rebuilds the mapping between nozzle capacitance and distance from the sheet.
  • Press F1 on the height controller and follow the on-screen prompts to redo the floating-head calibration.
  • If the calculated value is negative, enter it as the parking coordinate in the height controller — negative on a bus system, positive on a non-bus system.
  • A datum capacitance increase under 1000 can be absorbed automatically by the height controller's real-time calibration, which compensates thermal drift.
  • A datum capacitance decrease under 1000 is the same thermal-drift case — let the real-time calibration compensate it.
  • If the Z travel in the height controller is configured correctly, open the platform configuration tool and check whether a separate Z travel has been enabled for high and low tables.
  • Jog the head down and hold it about 3 mm above the sheet, then watch the DIF reading.
  • A DIF value above 30 proves there is electromagnetic interference in the system. Power down the XY servos, the compressor, the VFD and the other heavy consumers, then re-check whether DIF falls below 30.
  • Above 30, go straight to the machine's earthing rather than the sensor.
  • Watch DIF for about 10 seconds and judge the maximum value, not the average — spikes are what trip the alarm.
  • Close the shutter and simulate a cut with the gas on, watching whether the head jitters. That separates a gas/mechanical cause from a beam cause.
  • If the head does not jitter with gas on, the motion and gas sides are clean and the fault is on the beam side.
  • If the head does jitter with gas on, the sensing head may be damaged or badly seated — refit it or replace the affected part.
  • That pattern points to poor contact in the sensing head — replace the sensing head and retest.
  • Poor contact in the ceramic body — replace it and retest before touching parameters.
  • An RF cable problem — replace the cable and retest.
  • Also check that the RF cable is the original one from the controller vendor; third-party cables are a recurring cause here.
  • If the capacitance changes by less than 100 when gas is switched on and off, gas is not what is triggering the alarm.
  • A datum capacitance alarm at the very start of a job: check whether the sheet is film-covered.
  • An alarm that only appears after cutting for a while is probably thermal drift — diagnose it from the size of the capacitance change.